RShunt = R1 = VFsr / IFsr
Where: VFsr = Full scale reading (in Volts)
IFsr = Relative full scale current (in Amps)
Example: For a meter with a 2V full scale input (1.999 full
scale reading) and a desired full scale display reading of
1000 (with an input of 20mA), VFsr = 1.000 Volts
RShunt = 1.000V/(0.020 – 0.004)A
RShunt = 1.000V/0.016A = 62.5 Ohms
To calibrate the circuit of Figure 7, perform the following:
1. With 4mA applied, adjust the 50k7 potentiometer (R2) to
display a reading of "000" (assuming that is the desired
reading).
2. With 20mA applied, adjust the gain-adjust potentiometer on
the back of the meter to display a reading of "1999". For different full
scale readings, alter the RShunt value accordingly.
4-20mA R1
(+) IN HI
DMS-30LCD-1-5
8
REF OUT
ANA COMM
(–) IN LO
1
R2
+5V SUP
50k
3
5V RET
7
REF IN
120 VAC
DATEL
UPA-5/500
AC to DC Converter
Figure 7. 4-to-20mA Current Loop Operation
(5V-Powered Models)
6. Power Supply Monitoring: A popular application for DATEL’s low-
power LCD meters is monitoring the supply voltage in battery-oper-
ated portable equipment. Figure 8 demonstrates how a 9V-powered
DMS-30LCD can be used to monitor its own supply. The meter used
is the DMS-30LCD-1-9. A three-resistor voltage divider is used to
attenuate the battery voltage and also to satisfy the requirement that
the input voltages applied to pins 12 and 11 be at least 1.5 Volts above
and below the battery voltage applied to pins 1 (+BATTERY) and 3
(–BATTERY). The divider should be designed so that 1/10th the bat-
tery voltage falls across the inputs to the meter:
DMS-30LCD Series
3½ Digit, LCD Display Digital Panel Voltmeters
R2
= 0.1
(R1 + R2 + R3)
Therefore, the 9V battery voltage appears to the meter inputs as 0.9V.
With the decimal point moved to its DP2 position
(pin 5 tied to pin 3), the meter reads 9.00 Volts.
The circuit can be calibrated by first measuring the actual battery volt-
age with another meter and then adjusting the gain-adjust potentiom-
eter on the back of the DMS-30LCD until a similar reading is obtained.
If possible, the resistors in the divider should be ±1% metal-film types
with TCR’s less than 50ppm/°C.
8
REF OUT
DMS-30LCD-1-9
11
(+) IN HI
7
REF IN
1
+BAT
9V
BATTERY
3
–BAT
12
(–) IN LO
5
DP2
R1
45.3k
R2
10.1k
R3
45.3k
Figure 8. Power Supply Monitor
(9V-Powered Models)
7. External Gain Adjustment: Connect REFERENCE OUT
(pin 8) to REFERENCE IN (pin 7) for normal, factory calibrated, opera-
tion. Use the +1.23V REFERENCE OUT (pin 9) for applications need-
ing external gain adjustment. Figure 9 shows the wiring configuration
for each model. Calibration is performed with a precise, near-full-scale,
input voltage.
OUT
VOLTAGE
12 CALIBRATOR
COM
For 5V models tie
(–) IN LO to pin 3
11
(+) IN HI
3
5V RET
12
(–) IN LO
10
ANA COMM
For 9V models tie
(–) IN LO to pin 10
DMS-30LCD
8
7
9
NC
REF IN 1.23V REF
8.45k, 1%
1k
10 to 20 Turns
1k
8.45k, 1%
10 to 20 Turns
Connections
for ±2V and
±20V models
Connections
for ±200mV
models
Figure 9. External Gain Adjustment