G9SX-LM
Connecting Expansion Units
• The G9SX-EX and G9SX-EX-T Expansion Units can be connected
to the G9SX-LM@) to increase the number of safety instantaneous
outputs.
• When the G9SX-EX-T is connected, it will operate in the same way
as G9SX-EX.
• A maximum of five Expansion Units can be connected to one
G9SX-LM@. This may be a combination of G9SX-EX
Instantaneous types and G9SX-EX-T OFF-delayed types.
• Remove the terminating connector from the receptacle on the
G9SX-LM@ and insert the Expansion Unit cable connector into the
receptacle. Insert the terminating connector into the receptacle on
the Expansion Unit at the very end (rightmost).
• When Expansion Units are connected to an Advanced Unit, make
sure that power is supplied to every Expansion Unit. (Refer to the
following diagram for actual
• Expansion Unit connection.)
T31 T32 T33 M1 D12 D22 D11 D21
T11 T12 T61 T62 M2 Y1 Y2 A1
G9SX-LM224-F10
24VDC
PWB
FB
T1
T2
T6
T7
EI
3.6
3.2
4.2 4.75.3 6
6.6
3
7.3
2.8
8.4
2.4 2.2 2 109.3
SPD
ES
ERR
AND
MOD
DS
No.
T21 T22 T71 T72 T41 T42 L1 A2
X1 X2 X3 X4 S14 S24 ES1 ES2
Termination
connector
Setting Procedure
(1) Reset Mode
Set the reset mode using feedback/reset input terminals T31, T32,
and T33.
Auto reset mode is selected when terminal T32 is shorted to 24 V and
manual reset mode is selected when terminal T33 is shorted to 24 V.
Auto reset mode
Manual reset mode
KM1
KM2
KM3
KM4
+24V KM5
Reset
switch
KM1
KM2
KM3
KM4
KM5
+24V
T31 T32 T33
T31 T32 T33
G9SX-LM@
Expansion Units
(2) Cross Fault Detection
When connecting safety door switches to safety input and enabling
input, cross fault detection can be switched through the Y1 and Y2
terminals.
When the Y1 terminal is open, a cross fault of enabling inputs
between T11 and T12, and T21 and T22 is detected. When the Y2
terminal is open, a cross fault of safety inputs between T61 and T62,
and T71 and T72 is detected. When a cross fault is detected, the
following conditions occur:
a.The safety instantaneous outputs, safety speed detection
outputs, and logical AND connection outputs lock out.
b.The LED error indicator is lit.
c.An error output (auxiliary output) is turned ON.
When connecting safety sensors such as safety light curtains to
enabling input, be sure to connect the Y1 terminal to +24 V. When
connecting safety sensors to safety input, be sure to connect the Y2
terminal to +24 V. If not connected, G9SX-LM@ will detect it as an
error.
Cross fault
detection
Wiring of enabling
inputs and safety
inputs
Enabling input
Safety input
+24V
+24V
OFF
Using 1 safety input
channel
+24V
T11 T12 T21 T22 Y1
+24V
+24V
+24V
T61 T62 T71 T72 Y2
+24V
+24V
Using 2 safety input
channels
+24V
T11 T12 T21 T22 Y1
+24V
T61 T62 T71 T72 Y2
ON
Using 2 safety input
channels
T11 T12
Open
T21 T22 Y1
T61 T62
Open
T71 T72 Y2
Note: When using Type 4 safety sensor as a safety input, turn OFF the cross fault detecting function and connect dual-channel output from the
sensor to safety inputs terminal.
8