DatasheetQ Logo
Electronic component search and free download site. Transistors,MosFET ,Diode,Integrated circuits

G9SX-EX221-F10-RC 查看數據表(PDF) - OMRON Corporation

零件编号
产品描述 (功能)
生产厂家
G9SX-EX221-F10-RC
Omron
OMRON Corporation Omron
G9SX-EX221-F10-RC Datasheet PDF : 28 Pages
1 2 3 4 5 6 7 8 9 10 Next Last
G9SX-LM
(3) Setting Logical AND Connection
When connecting two or more Units by logical AND connection, set
the logical AND connection preset switch on the Unit that is on the
input side to AND.
Unit A
L1
A2
T41 T42
Unit B
AND
OFF
AND
OFF
Back
3.6 3.2
6.66
3
7.3
2.8
2.4
2.2
8.4
2 10 9.3
SPD
AND
OFF
T41/T42
Switch
Note: 1. A setting error will occur and Unit B will lock out if the logical
AND setting switch on the Unit is set to OFF.
2. Set the logical AND setting switch on Unit A to OFF or the
output of Unit A will not turn ON.
(4) Low-speed detection settings
To set a threshold value of low-speed detection frequency, use low-
speed detection settings switches (one each on the front and back of
the Unit). The Unit operates normally only when the preset values on
both switches agree. When the preset values of both switches do not
agree, an error occurs.
Front
Back
Switch
T31 T32 T33 M1 D12 D22 D11 D21
T11 T12 T61 T62 M2 Y1 Y2 A1
G9SX-LM224-F10
24VDC
PWB
FB
T1
T2
T6
T7
EI
3.6
3.2
4.2 4.75.3 6
6.6
3
7.3
2.8
8.4
2.4 2.2 2 109.3
SPD
ES
ERR
AND
MOD
DS
No.
T21 T22 T71 T72 T41 T42 L1 A2
X1 X2 X3 X4 S14 S24 ES1 ES2
3.6 3.2
6.66
3
7.3
2.8
2.4
2.2
8.4
2 10 9.3
SPD
AND
OFF
T41/T42
Switch
For setting position of preset switches, see the following
description:
3.6 4.2 4.75.3 6
3.2
6.6
3
7.3
2.8
8.4
2.4
9.3
2.2 2 10
3.6 4.2 4.75.3 6
3.2
6.6
3
7.3
2.8
8.4
2.4
9.3
2.2 2 10
SPD
Example 1: Low-speed
detection frequency 2 Hz
setting
Notch
SPD
Example 2: Low-speed
detection frequency 4.2 Hz
setting
(5) Response performance regarding speed detection
The response time of the entire system regarding speed detection
can be calculated by the following formula:
Ts = Tp + Tf + Tr + Tm
Ts : Response time of the entire system
Tp : Response time of the proximity sensor
Tf : Frequency detection time of G9SX-LM
Tr : Response time of G9SX-LM
Tm : Response time of the machine
• Frequency detection time of G9SX-LM (Tf)
The time taken to detect frequency at the rotation detection input
section of G9SX-LM.
Detection time differs depending on the input frequency.
For details, see the diagram below for the characteristics data.
• Response time of proximity sensor (Tp)
Calculation formula is as follows:
Tp = 1 / F (s)
F : Response frequency of the proximity sensor connected to G9SX-LM
Relationship between input frequency and frequency detection time (Example of characteristics data)
Set value of low-speed detection frequency (See the table below.)
1 100
1000
900
800
700
600
500
400
300
200
100
2
4
6
8
10
14
20
28
40
50
Frequency detection time (Reference value)
Set value of low-speed
detection frequency
2 Hz
2.2 Hz
2.4 Hz
2.8 Hz
3 Hz
3.2 Hz
3.6 Hz
4.2 Hz
4.7 Hz
5.3 Hz
6 Hz
6.6 Hz
7.3 Hz
8.4 Hz
9.3 Hz
10 Hz
Frequency detection time
(Reference value)
1000 ms max.
910 ms max.
835 ms max.
715 ms max.
670 ms max.
625 ms max.
560 ms max.
480 ms max.
430 ms max.
380 ms max.
350 ms max.
305 ms max.
275 ms max.
240 ms max.
220 ms max.
200 ms max.
• Response time of G9SX-LM (Tf)
Tr = 15ms max.
• Response time of the machine (Tm)
The time from when the machine receives a stop signal to the time
when the machine's hazardous part stops.
9