General Purpose Fuses
JLS Class J Fuses
600 VAC  •  Fast Acting  •  1 – 600 Amperes
JLS series fuses provide space saving, fast acting overload and short-
circuit protection for non-inductive loads. When used for motors or other
inductive loads, the ampere rating of JLS series fuses must be increased
to prevent nuisance opening on in-rush currents. In such applications, JLS
fuses may provide only short-circuit protection. Con­sid­er using Littelfuse
POWR-PRO® JTD or JTD_ID series time-delay fuses in such circuits.
Applications
General purpose circuits with little or no motor load.
Resistive loads, such as resistance electric heat.
Loads requiring fast acting overload protection, such as equipment
containing solid-state devices.
Space Saving
• JLS fuse characteristics are similar to KLNR/KLSR fast acting Class
RK1 fuses, but dimensionally are much smaller.
Safety
• 200,000 A.I.R. — Reliable interruption of all overcurrents up to
200,000 amperes.
• Extremely current-limiting — Stops dam­ag­ing short-circuit current
faster than any mechanical pro­tec­tive device.
• Fast acting — Provides fast acting protection to equipment such as
variable speed drives, rectifiers and other equip­ment containing surge
sensitive com­po­nents.
Longer Equipment Life
• Current-limiting design reduces damage to equip­ment caused by
heating and magnetic effects of short-circuit currents.
Economical
• Extremely current-limiting design often permits use of readily
available, less costly equipment.
• Manufacturers of equipment containing dual voltage devices can
simplify manufacturing and reduce inventory by stan­dard­iz­ing on 600
volt JLS fuses and Class J fuse blocks for all AC voltage ratings.
Easy to use
• 200,000 A.I.R. rating minimizes need for short-circuit cal­cu­la­tions.
NOTE: Littelfuse JLS fuses are not time-delay fuses. For ap­pli­ca­tions
where short-duration surg­es and spikes may cause nuisance fuse
opening, consider the use of Littelfuse POWR-PRO JTD or JTD_ID
series time-delay fuses.
Specifications
Voltage Ratings:
Interrupting Ratings:
Ampere Range:
Approvals:
600 Volts AC
200,000 amperes rms symmetrical
1 – 600 amperes
Standard 248-8, Class J
UL Listed (File No: E81895)
CSA Certified (File No: LR29862)
QPL: Federal Specification No: WF-1814
Ampere Ratings
1
25
60
125
300
3
30
70
150
350
6
35
80
175
400
10
40
90
200
450
15
45
100
225
500
20
50
110
250
600
Example part number (series & amperage): JLS 110
Recommended Fuse Blocks
LPSJ series, LJ600 series
Refer to the Blocks and Holders section of this catalog for additional in­for­ma­tion.