Current Transducer LA 55-TP/SP27
For the electronic measurement of currents : DC, AC, pulsed...,
with a galvanic isolation between the primary circuit (high power)
and the secondary circuit (electronic circuit).
IPN = 50 A
Electrical data
IPN
Primary nominal r.m.s. current
IP
Primary current, measuring range
RM Measuring resistance
with ± 12 V
with ± 15 V
@ ± 50 Amax
@ ± 100 Amax
@ ± 50 Amax
@ ± 100 Amax
ISN Secondary nominal r.m.s. current
KN Conversion ratio
VC Supply voltage (± 5 %)
IC
Current consumption
Vd
R.m.s. voltage for AC isolation test, 50 Hz, 1 mn
Vb
R.m.s. rated voltage
50
A
0 .. ± 100
A
RM min
RM max
0
210 Ω
0
30 Ω
30
320 Ω
30
90
Ω
25
mA
1 : 2000
± 12 .. 15
V
10 (@±15V ) +IS m A
3.6
kV
600
V
Features
• Closed loop (compensated) current
transducer using the Hall effect
• Mounted on printed circuit board
• Insulated plastic case recognized
according to UL 94-V0.
Special features
• IP = 0 .. ± 100 A
• KN = 1 : 2000
• Vd = 3.6 kV
• TA = - 40°C .. + 85°C.
• Potted.
Accuracy - Dynamic performance data
X
Accuracy @ IPN, TA = 25°C
@ ± 15 V (± 5 %) ± 0.65
%
@ ± 12 .. 15 V (± 5 %) ± 0.90
%
εL
Linearity
< 0.15
%
Typ Max
IO
Offset current @ IP = 0, TA = 25°C
± 0.1 m A
IOM Residual current 1) @ IP = 0, after an overload of 3 x IPN
± 0.2 m A
IO T
Thermal drift of IO
- 25°C .. + 85°C ± 0.1 ± 0.3 m A
- 40°C .. - 25°C ± 0.2 ± 0.5 m A
t ra
tr
di/dt
f
Reaction time @ 10 % of IPN
Response time 2) @ 90 % of IPN
di/dt accurately followed
Frequency bandwidth (- 1 dB)
< 500
<1
> 200
DC .. 200
ns
µs
A/µ s
kHz
General data
TA
Ambient operating temperature
TS
Ambient storage temperature
R S Secondary coil resistance @ TA = 85°C
m Mass
Standards 3)
- 40 .. + 85
°C
- 50 .. + 90
°C
140
Ω
35
g
EN 50155
Advantages
• Excellent accuracy
• Very good linearity
• Low temperature drift
• Optimized response time
• Wide frequency bandwidth
• No insertion losses
• High immunity to external
interference
• Current overload capability.
Applications
• AC variable speed drives and servo
motor drives
• Static converters for DC motor drives
• Battery supplied applications
• Uninterruptible Power Supplies
(UPS)
• Switched Mode Power Supplies
(SMPS)
• Power supplies for welding
applications.
Notes : 1) The result of the coercive field of the magnetic circuit
2) With a di/dt of 100 A/µs
3) A list of corresponding tests is available.
001127/2
LEM Components
w w w.lem.com